3 pole manual reset high limit, fail safe
Housing dimensions: dia 45 x 44.3 mm
Capillary: copper, capillary length 250mm or 900 mm, 150 mm long PVC sleeve on capillary.
Electrical rating | |
---|---|
Voltage | |
Max operating temperature (°C) | |
Opening temperature (°C) | |
Min resettable temperature (°C) | |
Capillary length (mm) | |
Bulb diameter (mm) | |
Bulb length (mm) |
TECHNICAL FEATURES
Housing dimensions: dia 45 x 44.3 mm
Capillary: copper, capillary length 250mm or 900 mm, 150 mm long PVC sleeve on capillary. Capillary minimum bending radius 5 mm. For technical reasons, we do not recommend to use capillary length longer than 900 mm.
Bulb: Copper, corkscrew type for temperatures from 60 to 130°C(140 to 266°F),tubular dia 6 mm from 130°C to 170°C (266 to 338°F).
Temperature sensing element: Liquid-filled thermostatic assembly whose boiling causes tripping of the contact. Therefore, unlike liquid filled systems, these thermostats are sensitive to atmospheric pressure, and their reaction time is slower.
Terminals: 6.35 x 0.8 quick connect terminals Adjustment: fixed setting
Mounting: Backside legs, 2 M4 screws, holes distance 60 mm
Manual reset: fail safe action, center button
Rating: 3 x 16A 250VAC, 3 x 10A 400VAC, resistive (10000 cycles) 3 x 25A 250VAC, 3 x 16A 400VAC (300 cycles)
Contacts: ST, open on temperature rise (snap action contact)
Max ambient temperature on head: 150°C(302°F)
Main references
Reference |
Calibration Temperature (°C/°F) |
Minimum resettable temperature (°C/°F) |
Capillary length (mm) |
Bulb diameter (mm) |
Bulb length (mm) |
Max temperature on bulb (°C/°F) |
820060090CI61001 | 60±5°C/140±41°F | 20°C/68°F | 900 | 6 | 50 | 90°C/194°F |
820060090CA61001 | 60±5°C/140±41°F | 20°C/68°F | 250 | 6 | 50 | 90°C/194°F |
820070100CI61001 | 70±5°C/158±41°F | 30°C/86°F | 900 | 6 | 50 | 100°C/212°F |
820080110CI61001 | 80±5°C/176±41°F | 40°C/104°F | 900 | 6 | 50 | 110°C/230°F |
820090120CI61001 | 90±5°C/194±41°F | 50°C/122°F | 900 | 6 | 50 | 120°C/248°F |
820110140CI61001 | 110±5°C/230±41°F | 70°C/158°F | 900 | 6 | 50 | 140°C/284°F |
820130160CI61001 | 130±6°C/266±42.8°F | 90°C/194°F | 900 | 6 | 60* | 160°C/320°F |
820150180CI61001 | 150±7°C/302±44.6°F | 110°C/230°F | 900 | 6 | 60* | 180°C/356°F |
820170200CI61001 | 170±7°C/338±44.6°F | 130°C/266°F | 900 | 6 | 60* | 200°C/392°F |
Downloads
Related products
FIRE DETECTION
Remote temperature control boxes
Dia. 30 to 70mm pipe mounting thermostat IP55 with 2 built-in pilot lights
Disc temperature limiters
Bulb and capillary temperature limiters
Remote temperature control boxes
Electronic control thermostats
Remote temperature limiter boxes
Technical informations associated to this product
-
Electrical contacts
As numerous mechanisms exist, we decided not to distinguish on the basis of constructive technique, but according to their operation speed, which is the key element. -
Description of temperature controls
Used as control thermostats or as a safety thermostat with manual reset, these thermostats have a disc made of two different metals laminated together for temperature sensing element. These two metals have different expansion coefficients. -
Electrical protection classes
The housings are designed to protect electrical equipment located inside. This protection must be considered in the electrical and environmental angles.) -
Thermostats installation
The proper functioning of a thermostat depends primarily on the correct choice of the component, but also the conditions of its installation. Conditions used to calibrate regulating and control equipment in the factory are always ideal laboratory conditions, ensuring measurement accuracy and repeatability. These conditions are rarely those found in practice when installing thermostats. However, with a minimum of constraints, it is possible to optimize assemblies.