Power formula OHM’S law
P = Power in watts U = Voltage
U = Voltage P = UI R = Resistance in ohms U = RI
I= Current in amperes I= Current in amperes
I= P/U  U= P/I I= U/R R= U/I P= U2 /R R= U2 /P

 

Heating elements connections

(Heating elements resistance “r” of unit power “p” with nominal voltage “U”)

 

Parallel wiring Serial wiring

 

Quantity of elements (n) Total resistance (R) Total power (P)
2 R = r/2 p = 2p
3 R = r/3 p = 3p
X R = r/x p =xp
NOTE: Watt density (W/cm2) for each element is unchanged
Quantity of elements (n) Total resistance (R) Total power (P) Heating element Watt density (w/cm2)
2 R = 2r p = p/2 Devided by 4
3 R = 3r p = p/3 Devided by 9
X R=Xr p = p/x Devided by x2

 

Delta and star element connections

Delta connection Star connection
Delta (triangle) connection:
The voltage supplied to the heating elements is the same than the power supply voltage measured between phases : U= Un
Supply voltage (U) 230V,
3 phases
230V,
3 phases
400V,
3 phases
400V,
3 phases
Heating elements nominal voltage (Un) 230V 400V 230V 400V
Watt density (W/cm2) No change  in watt density Watt density is divided by 3 Watt density is multiplied by 6 No change in
watt density
Total power (P) Total power is 3 time nominal power of one
heating element (P=3 p)
Total power is divided by 9.lt
is 1/3 of nominal power of one heating element (P= p/3)
Total power is 9 time nominal power of one
heating element (P=9 p)
Total power is 3 time nominal power of one
heating element
(P= 3p)
comments No problem solution This can be used a reduced power step by using a
Star/ Delta (triangle)
connection system
Never use Fire hazard! This is the most common configuration
Star connection :
The voltage supplied to the heating elements is the same than the power voltage divided byv3: U=1.737Un).
Example: power supply is 400V, the heating element is energized with 400/1.737= 230V
Supply voltage (U) 230V,
3 phases
230V,
3 phases
400V,
3 phases
400V,
3 phases
Heating element! nominal voltage (Un) 230V 400V 230V 400V
Watt density (W/cm2) Watt density is divided by 3 Watt density is divided by 9 No change in
watt density
Watt density is divided by 3
Total power (P) Total power is 1/3 of total possible power : it is the same than one heating element (P=p) Total power is 1/9 of total possible power.
1/3 nominal power of one heating element (P= 1/3 p)
Total power is 3 time nominal power of one
heating element
(P=3p)
Total power is 1/3 of total possible power. it is the same than one heating element (P=p)
comments Not recommended Not recommended This is the most standard connection, allows the same heaters to be used with 400V star connection or 230V delta connection without
power change